multicondPower capacitors |
![]() |
| Illustration similar |
Power from 1.5 to 37 kvar
Capacitor nominal voltage of 280, 440, 480, 525 or 690 V
1-phase or 3-phase design
High level of safety through drying technology and all-phase overpressure disconnector
Including compact discharge resistor
Long working life
| multicond premium UHPC |
multicond basic UHPC |
multicond basic HPC |
|||
| Rated voltage | frequency: |
Un = 280, 440, 480,525 oder 690 V | 50/60 Hz |
||||
| Maximum permissible operating voltage: |
1,0 x Un continous | 1,1 x Un an 8 hours/day |
1,15 x Un an 30 minutes/day1,2 x Un 200 x 5 minutes | 1,3 x Un an 200 x 1 minute |
||||
| Maximum permissible operating current: |
1,5 x In bei 0 – 15,9 kvar | 2,0 x In bei > 15,9 kvar |
||||
| Maximum inrush current: | 400 x In | ||||
| Capacity tolerance: | + / - 5 % | ||||
| Power dissipation: | < 0,20 W / kvar, without discharge resitors | < 0,25 W / kvar, without discharge resitors | < 0,25 W / kvar, without discharge resitors | ||
| Voltage test (terminal – terminal): |
2,15 x Unenn (AC), 2 sec |
||||
| Voltage test (terminal – housing): |
≤ 600 V : 3000 V (AC), 10 sec | > 600 V : 6000 V (AC), 10 sec |
||||
|
Working life:
|
Temperature class: max.ambient highest average highest average |
Temperature class: max.ambient highest average highest average |
Temperature max.ambient highest average highest average |
||
|
Temperature class: max.ambient highest average highest average |
Temperature class: max.ambient highest average highest average |
Temperature max.ambient highest average highest average |
|||
| Cooling: | Natural cooling | ||||
| Permissible humidity: | 95% | ||||
| Maximum deployment altitude: | 4000 m above sea-level | ||||
| Installation site, installation position: |
inside, anywhere |
||||
| Attachment: | M12 threaded bolts on ground | ||||
| Safety features: | - Dry technology, - resin-filled - Self-restoring - Overpressure disconnector all-pole - SF6-free, PCB-free |
- Dry technology, - resin-filled - Self-restoring - Overpressure disconnector all-pole - SF6-free, PCB-free |
- Dry technology, - gas-filled - Self-restoring - Overpressure disconnector all-pole - SF6-free, PCB-free |
||
| Housing: | Aluminium | ||||
| Degree of protection: | IP 20 | ||||
| Dielectric: | Polypropylene | ||||
| Terminal strips: |
Double-sided terminal strip, safe from finger-touch
|
||||
| discharge: |
Discharge resitors on outside of strip
|
||||
| Standards: | IEC 60831-1 + 2, EN 60831-1 + 2, VDE 0560-46 +47 | ||||