multicab-FFixed capacitors |
![]() |
DIMENSIONS (H x W x D in mm):
S2 (800 x 800 x 400)
S3 (1200 x 800 x 400)
Power from 5 to 60 kvar
Inductor factors 5.5, 7 or 8 % and 12.5 or 14 %
Capacitor rated voltage with 440 V or 525 V
Optional: Contactor and NH isolator
DEVICE TYPE
SWSH p = 5.5, 7 or 8 %
SWSB p = 12.5 or 14 %
| Rated voltage | frequency: | Un = 400 V | 50 Hz |
| Maximum permissible operating voltage: | Un = 400 V ± 10 % |
| Maximum permissible operating current: | 1.3 x I n permanently |
| CAPACITORS: | Low-loss multicond-UHPC power capacitors, MTK technology |
| Capacitor rated voltage: | Urated = 440 V (SWSH), Urated = 525 V (SWSB) |
| Discharge of capacitors: | Discharge resistors t < 60 s, optional discharge inductors t < 3 s |
| FILTER CIRCUIT INDUCTORS: | Linear filter circuit inductors to avoid resonances in networks with harmonics, integrated temperature monitoring |
| Inductor factors: | p=5.5,7 or 8 & (SWSH), p=12.5 or 14 % (SWSB) |
| HOUSING DESIGN: | Sheet steel cabinet, inside and outside painted in color RAL 7035 (other colors on request), module plates galvanized |
| Protection type: | IP 20 (IP 54 on request), the components used correspond to BGV-A2 |
| AMBIENT TEMPERATURES: | + 40 °C highest value, briefly + 35 °C in 24-hour average, + 20 °C in annual average, – 10 °C lowest value |
| OPTION: Back-up fuse additional NH: | With NH isolator and NH fuses |
| OPTION: Switching element additional LS: | Capacitor contactors Ucontrol = 230 V, 50 Hz, control voltage transformer required if operating voltage deviates |
| OPTION: Apparent current relay additional LSR: |
Apparent current relay additional LSR, connecting and disconnecting is done by contactor |
>>> Control voltage transformer required for deviating operating voltage
| Switching delay: 60 s |